GODIYMODULES Standard Edition

GODIYMODULES Digital Display Meter Standard Edition User Manual

Model: Standard Edition

1. Introducción

This manual provides comprehensive instructions for the installation, operation, and maintenance of the GODIYMODULES Digital Display Meter, Standard Edition. This universal analog input display meter is designed to work with various sensors that provide analog output, such as temperature transmitters, frequency converters, motor speed sensors, pressure transducers, and liquid level sensors. Please read this manual thoroughly before operating the device to ensure correct usage and optimal performance.

2. Producto terminadoview

The GODIYMODULES Digital Display Meter is a versatile panel meter capable of displaying actual physical quantities based on analog input signals. It supports both current and voltage inputs, with default adaptations for 0-10V, 2-10V, 0-20mA, and 4-20mA. The meter features a 0.55-inch 4-digit digital tube display for clear readings and intuitive button controls for parameter settings.

Frente view of the GODIYMODULES Digital Display Meter

Figura 2.1: Frente view of the GODIYMODULES Digital Display Meter, showing the digital display and control buttons.

3. Características principales

  • Universal Analog Input: Compatible with 0-10V, 2-10V, 0-20mA, and 4-20mA signals. Adaptable to other ranges via polarization and gain parameters.
  • Amplia gama de fuentes de alimentación: DC6~25V for standard and RS485 versions; DC8~25V for relay output version.
  • Protección de energía: Features anti-reverse connection and surge protection.
  • Single Analog Input: Supports either voltage o entrada actual.
  • Impedancia de entrada: >30kΩ for voltage type, <250Ω for current type.
  • Pantalla clara: 0.55 inch, 4-digit digital tube display.
  • Configuración sencilla de parámetros: Built-in buttons for convenient configuration.
  • Diseño compacto: Mechanical size of 79 x 43 x 25 mm, with an installation opening of 76.5 x 39.5 mm.
  • Optional RS485 Interface: (Available in RS485 version) Supports Modbus-RTU protocol for multi-meter communication.
  • Optional Relay Output: (Available in relay output version) One normally open relay output, load capacity: 3A30VDC/3A250VAC.

4. Configuración

4.1. Instalación mecánica

The meter is designed for panel mounting. Ensure the installation opening in your panel matches the specified dimensions.

  • Tamaño mecánico: 79 mm (Length) x 43 mm (Width) x 25 mm (Depth)
  • Apertura de instalación: 76.5 mm (largo) x 39.5 mm (ancho)
Parte superior en ángulo view of the meter showing buttons and terminal block

Figura 4.1: Parte superior en ángulo view of the meter, illustrating the physical form factor and button layout.

Angular view of the meter showing buttons and terminal block from another perspective

Figura 4.2: Otro ángulo view of the meter, providing a clearer look at the control buttons and terminal block.

4.2. Instrucciones de cableado

Refer to the common wiring diagram for proper connection of power supply and analog input. Ensure the power supply voltage está dentro del rango especificado para evitar daños.

Atrás view of the meter with wiring diagram and terminal labels

Figura 4.3: Atrás view of the meter showing the wiring diagram for power, ground, and analog input terminals.

Descripciones de terminales:

  • ENERGÍA: Positive power supply input (DC6~25V for standard/RS485, DC8~25V for relay version).
  • TIERRA: Ground connection for power supply and analog input.
  • AI: Volumen analógicotage Input (0-10V, 2-10V).
  • mamá: Analog Current Input (0-20mA, 4-20mA).
  • CAROLINA DEL NORTE: Not Connected.
  • RS485 (R, T, S): For RS485 communication (available in RS485 version only). R indicates data reception, T indicates data transmission, S indicates signal ground.
  • Relay (NO): Normally Open relay output (available in relay output version only).

Importante: The meter supports either voltage input (AI) or current input (mA), but not both simultaneously. Connect your sensor output to the appropriate terminal.

5. Instrucciones de funcionamiento

5.1. Button Functions and Display States

The meter features four buttons for navigation and parameter adjustment: SET, UP (↑), DOWN (↓), and OK. The 4-digit digital display shows the measured value or parameter settings.

Funciones de los botones:

  • CONJUNTO: Enters parameter setting mode or cycles through parameter groups.
  • UP (↑): Aumenta el valor o navega hacia arriba en los menús.
  • DOWN (↓): Disminuye el valor o navega hacia abajo en los menús.
  • Aceptar: Confirms selection or saves parameter changes.

Digital Tube Display State Transition Diagram:

The meter typically displays the measured value. Pressing the SET button allows entry into the parameter setting menu. Use UP/DOWN to navigate and OK to select/confirm. Pressing SET again will exit the parameter setting mode or move to the next parameter group.

5.2. Configuración de parámetros

The meter's functionality is configured through various parameters organized into groups. To enter the parameter setting mode, press the COLOCAR Botón. Utilice el UP y ABAJO buttons to adjust values and OK Para confirmar, presione COLOCAR to move between parameters or exit.

5.2.1. F0-0 Displayed Quantity Collection Parameters

ParámetroScope and DescriptionValores predeterminadosLeer/Escribir
F0-0Displayed value monitoring: Displays the current collected value. Range: 0-100.0%0.0Solo lectura
F0-1Display accuracy: The number of decimal places displayed in the collected value. Range: 0-31Leer/Escribir
F0-2Show minimum: The minimum value corresponding to "acquisition value" 0%. Range: -9999 to 99990Leer/Escribir
F0-3Show maximum: The maximum value corresponding to the "acquisition value" is 100%. Range: -9999 to 99991000Leer/Escribir
F0-4Display range: The display range is F0-2 to F0-3. Starting from F0-2.0Leer/Escribir

Nota: The displayed value is a default percentage. You can set your own display range using F0-2 to F0-4.

5.2.2. F1-0 Parameter Group Configuration Parameters

ParámetroScope and DescriptionValores predeterminadosLeer/Escribir
F1-0Input type selection: 0: 0-10V or 0-20mA (corresponds to 0-100% of the acquisition value). 1: 2-10V or 4-20mA (corresponds to 0-100% of the acquisition value).0Leer/Escribir
F1-1Input filter time: The filtering time for the input signal. Range: 0-1000ms.200Leer/Escribir
F1-2Input offset: The offset value for the input signal. Range: 0-100.0%0.0Leer/Escribir
F1-3Input gain: The gain value for the input signal. Range: 0-100.0%100.0Leer/Escribir
F1-4Drop detection threshold: If the input value is not detected, the display will show "----". This parameter sets the threshold for detection. If the input value is less than this threshold, it is considered not detected. Range: 0-100.0% (Starting from V0.10)0.0Leer/Escribir

Nota: By setting the polarization parameter (F1-2) and gain parameter (F1-3), the meter can be adapted to other input ranges within 0-10V or 0-20mA.

5.2.3. F2-0 Parameter Group Relay Output Parameters (for Relay Output Version)

ParámetroScope and DescriptionValores predeterminadosLeer/Escribir
F2-0Relay output: 0: Normally open, 1: Normally closed.0Leer/Escribir
F2-1Condition type: 0: Greater than comparison value 1, 1: Less than comparison value 1, 2: Greater than comparison value 2, 3: Less than comparison value 2.0Leer/Escribir
F2-2Comparison value 1: The value used for comparison. Range: 0-100.0%50.0Leer/Escribir
F2-3Comparison value 2: The value used for comparison. Range: 0-100.0%0.0Leer/Escribir
F2-4Hysteresis interval: The hysteresis value to prevent frequent relay operation. Range: 0-100.0%5.0Leer/Escribir
F2-5Relay status when offline: 0: Keep current status, 1: When the offline value is less than the comparison value, the relay is closed, 2: When the offline value is greater than the comparison value, the relay is closed.0Leer/Escribir

Nota: These parameters are only applicable to the version of the meter equipped with a relay output. The Standard Edition may not include this feature.

5.3. RS485 Communication Parameters (for RS485 Version)

This section applies only to the Digital Display Meter with RS485 interface. It uses the standard Modbus-RTU protocol for communication.

Detailed diagram showing parameter settings for F0, F1, F2, and RS485 communication

Figura 5.1: Comprehensive parameter tables including F0, F1, F2, and RS485 communication settings.

ParámetroScope and DescriptionValores predeterminadosLeer/Escribir
F7-0Local address: The address of the meter in the Modbus network. Range: 1-2471Leer/Escribir
F7-1Baud rate: 0: 1200bps, 1: 2400bps, 2: 4800bps, 3: 9600bps, 4: 19200bps, 5: 38400bps.3Leer/Escribir
F7-2Data format: 0: 8N1 (8 data bits, 1 stop bit, no parity), 1: 8E1 (8 data bits, 1 stop bit, even parity), 2: 8O1 (8 data bits, 1 stop bit, odd parity), 3: 8N2 (8 data bits, 2 stop bits, no parity).0Leer/Escribir
F7-3Response delay: The delay time before the meter responds to a Modbus query. Used to prevent bus collisions in half-duplex communication. Range: 0-100ms.5Leer/Escribir
F7-4Communication type: 0: The display table is in the network host mode, 1: The display table is in the network slave mode, 2: The display table through the broadcast mode.0Leer/Escribir
F7-5Parameter interval: The interval time for the meter to send parameters. Range: 0-1000ms.100Leer/Escribir
F7-6Send recovery time: The time for the meter to send recovery parameters. Range: 0-1000ms.100Leer/Escribir
F7-7Software version number: Displays the current software version.1.00Solo lectura

Modbus-RTU Protocol Details:

The meter supports standard Modbus-RTU protocol. The communication parameters (address, baud rate, data format) must be configured correctly to match the master device. The image also shows a table of Modbus register addresses for various parameters (e.g., F0-0, F0-1, F1-0, etc.) which can be read or written via Modbus commands.

For detailed Modbus register addresses and functions, refer to the provided diagram (Figure 5.1) or the official Modbus communication guide for this device. Example: To read F0-0, use Modbus function code 03 (Read Holding Registers) with the corresponding address.

6. Mantenimiento

  • Limpieza: Utilice un paño suave y seco para limpiar la pantalla del medidor yasing. No utilice limpiadores abrasivos ni disolventes.
  • Ambiente: Ensure the meter is operated within its specified environmental conditions (temperature, humidity) to prolong its lifespan.
  • Conexiones: Periodically check all wiring connections for tightness and ensure they are free from corrosion.
  • Calibración: If accuracy issues are suspected, refer to the parameter settings for input offset and gain adjustment, or consult a qualified technician for recalibration.

7. Solución de problemas

ProblemaPosible causaSolución
El medidor no se enciende.No hay suministro de energía o volumen incorrectotage.Verifique las conexiones eléctricas y asegúrese del volumen.tage is within DC6~25V (or DC8~25V for relay version).
Display shows "----".No analog input signal detected or signal below F1-4 threshold.Verify sensor connection and output. Check F1-4 (Drop detection threshold) setting.
Lecturas incorrectas.Incorrect input type (F1-0), offset (F1-2), or gain (F1-3) settings. Sensor malfunction.Review F1-0, F1-2, F1-3 parameters. Check sensor calibration and output.
Fallo de comunicación RS485.Incorrect RS485 parameters (F7-0 to F7-4). Wiring issues.Verify F7-0 (Local address), F7-1 (Baud rate), F7-2 (Data format) match the master device. Check RS485 wiring (R, T, S).

8. Especificaciones

MarcaMÓDULOS DE GODIY
ModeloEdición estándar
Tipos de señal de entradaVolumentage (0-10V, 2-10V), Current (0-20mA, 4-20mA)
Power Supply (Standard/RS485)CC 6 ~ 25 V
Power Consumption (Standard/RS485)24 V/40 mA
Power Supply (Relay Output Version)CC 8 ~ 25 V
Power Consumption (Relay Output Version)24 V/50 mA
Impedancia de entrada (Voltage Type)> 30 kΩ
Input Impedance (Current Type)<250Ω
Mostrar0.55 inch, 4-digit digital tube
Tamaño mecánico79 x 43 x 25 mm
Apertura de la instalación76.5 x 39.5 mm
Peso50 gramos
RS485 Protocol (Optional)Modbus RTU
Salida de relé (opcional)1 Normally Open, 3A30VDC/3A250VAC