Coolmay QM3G-50FH-24MT/R

Manual del usuario del PLC combinado Coolmay QM3G-50FH HMI

Programmable Logic Controller with Touch Panel Industrial Monitor

1. Producto terminadoview

The Coolmay QM3G-50FH series is an integrated Human Machine Interface (HMI) and Programmable Logic Controller (PLC) designed for industrial automation applications. This device combines a touch panel display with a powerful PLC, offering a compact and efficient solution for control and monitoring tasks.

Key features include compatibility with Mitsubishi programming software (GX Developer, GX Works2), support for PID auto-tuning, and PWM modulation. The device is built with an ARM9 core and imported components for guaranteed quality.

Frente view of Coolmay QM3G-50FH HMI PLC Combo displaying a date and timer set screen.

Figura 1: Frente view of the QM3G-50FH HMI PLC Combo.

Trasero view of Coolmay QM3G-50FH HMI PLC Combo showing input/output terminals and communication ports.

Figura 2: Posterior view of the QM3G-50FH HMI PLC Combo, highlighting I/O and communication ports.

Modelos de productos

The QM3G-50FH series offers various configurations. The specific model covered in this manual is the QM3G-50FH-24MT/R.

  • QM3G-50FH-24MT: 5-inch HMI PLC all-in-one, 12 Digital Inputs (DI), 12 Digital Outputs (DO) with transistor outputs. Optional maximum 4 Analog Inputs (AD) and 2 Analog Outputs (DA). Includes 1 RS232, 1 RS485, 4 high-speed pulse outputs (100KHz, Y0-Y3), and 4 high-speed pulse outputs (10KHz, Y4-Y7).
  • QM3G-50FH-24MR: 5-inch HMI PLC all-in-one, 12 Digital Inputs (DI), 12 Digital Outputs (DO) with relay outputs. Optional maximum 4 Analog Inputs (AD) and 2 Analog Outputs (DA). Includes 1 RS232, 1 RS485.

Note: Analog input and output functions are optional and must be purchased separately. The number of selected analog channels cannot exceed the maximum quantity for the specific model.

Encimaview of different Coolmay QM3G HMI PLC models including QM3G-43FH, QM3G-50FH, QM3G-70FH, QM3G-70KFH, and QM3G-100FH.

Figure 3: Various QM3G HMI PLC All-in-one Product Models.

2. Configuración e instalación

2.1 Contenido del paquete

  • 1x HMI PLC all-in-one unit
  • Mounting hardware (clips/screws)
  • (Optional) Programming cables (USB-232 serial, 232 programming, Type-C HMI, Type-C PLC)

2.2 Dimensiones de montaje

Ensure adequate space for installation and ventilation. Refer to the diagram below for precise cutout and overall dimensions for the QM3G-50FH model.

Dimensional drawing for QM3G-50FH HMI PLC, showing front, side, and top views with measurements in millimeters. Cutout size: 143x86mm, Overall dimensions: 151x96x36mm.

Figure 4: QM3G-50FH Mounting Dimensions (Cutout size: 143x86mm, Overall: 151x96x36mm).

2.3 Cableado

All wiring should be performed by qualified personnel. Ensure the power supply is disconnected before making any connections. The device requires a DC24V input.

2.3.1 Fuente de alimentación y conexión a tierra

Connect the FG (Frame Ground), 0V (Negative), and DC24V (Positive) terminals as shown in the rear view diagram. Proper grounding is essential for stable operation and safety.

2.3.2 Cableado de entrada/salida digital

The digital input (X) is an externally powered DC24V sinker (passive NPN). The input signal is isolated from the power supply. Connect COM to the positive 24V of the external power supply while using. The digital output terminals are grouped, and each group is electrically isolated. For relay outputs, COM is common to the positive or negative. For transistor outputs, COM is common to the negative.

Diagram showing PLC internal output wiring, including pulse outputs (Y0-Y3, Y4-Y7) and common terminals.

Figure 5: PLC Internal Output Wiring Diagram (Diagram 14 from manual).

Equivalent circuit diagrams for PLC digital input, relay output, transistor output, and inductive load absorption circuit schematic.

Figure 6: Equivalent Circuit Diagrams for PLC I/O.

2.3.3 Analog Input/Output Wiring (Optional)

For models with analog capabilities, refer to the specific wiring diagrams. Analog inputs support various types including voltage (0-5V, 0-10V), current (0-20mA, 4-20mA), and temperature sensors (Thermocouple J/K, PT100, PT1000, NTC10K/100K). Analog outputs support voltage (0-5V, 0-10V) and current (0-20mA, 4-20mA).

Diagram showing PLC analog wiring for inputs (AD0-AD3) and outputs (DA0-DA1), with common ground connections.

Figure 7: PLC Analog Wiring Diagram (Diagram 15 from manual).

2.3.4 Puertos de comunicación

The device includes RS232 and RS485 communication ports. Ethernet and WIFI are optional features. Refer to the pin definitions for proper connection.

Table showing basic parameters for HMI PLC All-in-One, including digital I/O, analog I/O, and COM port options for different models.

Figure 8: Basic Parameters and Communication Port Options.

2.3.5 Programming Cable Connections

To program the HMI PLC, connect the appropriate programming cables to your computer and the device. The image below illustrates a typical setup.

Example wiring setup showing connections for USB-232 serial port cable, 232 programming cable, AC 220V, power supply (DC24), Type-C HMI programming cable, and Type-C PLC programming cable.

Figura 9: Example Programming Cable Connections.

3. Instrucciones de funcionamiento

3.1 Powering On and Initial Screen

Once properly wired and powered, the HMI PLC will boot up and display the configured interface. The touch panel allows for interaction with the system.

Video 1: Product demonstration showing HMI interface navigation and features, including system upgrade, full functions, and customizable options.

3.2 HMI Interface Navigation

The HMI features a touch-sensitive screen for navigating menus, inputting data, and monitoring processes. The interface can be customized using the programming software.

Two HMI PLC units from a side angle, displaying a control interface with checkboxes and numerical inputs, demonstrating the user interface.

Figure 10: HMI displaying a control interface.

3.3 PLC Programming

The PLC can be programmed using Mitsubishi software such as GX Developer (versions 8.86 and 8.52) and GX Works2. Refer to the respective software manuals for detailed programming instructions.

3.3.1 Analog Input Register Operation

Analog input register operation is 12-bit precision. Input values can be read from D0 to D400. The constant scan time is 100. For temperature inputs, the corresponding value is the temperature in degrees Celsius, with a decimal point. For exampPor ejemplo, 182.0°C se representa como 1820.

3.3.2 Analog Output Register Operation

Analog output register operation is 12-bit precision. Output channels (DA0-DA7) correspond to the analog output value. The set value range is 0-4000. For 0-20mA output, D8058.7=0. For 4-20mA output, D8058.7=1.

Programming reference and statement of power-down save, including sampling of analog inputs and analog output register details.

Figure 11: Programming Reference and Analog Register Details.

4. Mantenimiento

4.1 Cuidados generales

  • Mantenga el dispositivo limpio y libre de polvo y residuos. Utilice un paño suave y seco para limpiarlo.
  • Evite exponer el dispositivo a temperaturas extremas, humedad o luz solar directa.
  • Asegure una ventilación adecuada alrededor de la unidad para evitar el sobrecalentamiento.

4.2 Power-Off Hold Functions

The HMI PLC's device power-off maintenance is permanently maintained. All data in the HMI and PLC areas are not lost after the module is powered off. The real-time clock uses a rechargeable battery to ensure that the clock is current. All power-off hold functions must ensure DC24V. The voltage after the source is loaded is 23V or more, and the PLC power-on time is longer than 2 minutes, otherwise the power-off function will be abnormal.

4.3 Condiciones ambientales

The device is designed to operate within specific environmental parameters:

  • Temperatura de funcionamiento: 0°C - 50°C
  • Humedad relativa: 5% - 95% HR (sin condensación)
  • Temperatura de almacenamiento: -20°C - 70°C
  • Frecuencia de vibración: 10-57Hz, amplitude 0.035mm; 57Hz-150Hz, acceleration 4.9m/s² (10 times each on X, Y, Z, total 60 minutes each).

5. Solución de problemas

Esta sección ofrece orientación para problemas comunes. Para problemas complejos, contacte con el soporte técnico.

5.1 User Tips for Troubleshooting and Safe Operation

User tips for the QM3G-FH series HMI PLC, covering power supply, wiring, grounding, avoiding short circuits, and proper disposal.

Figure 12: Important User Tips.

  • Fuente de alimentación: Always use a regular power supply that matches the specified voltage (DC24V). Ensure the power supply output voltage is 18W or higher and 24V.
  • Alambrado: Before installation, tighten screws and clamp guides to avoid falling. Incorrect wiring can cause electric shock or circuit fault.
  • Toma de tierra: Properly ground the device. Improper grounding can cause abnormal operation. Do not drop metal shavings and wire tips into the control vent holes.
  • Cortocircuitos: Do not short-circuit the power supply. This can cause product malfunctions and faults.
  • Comunicación: Keep communication cables short (under 10m) and away from strong interference sources.
  • Potencia externa: The digital input is an externally powered DC24V leakage type (passive NPN). Connect to the positive 24V pole of the external power supply.
  • Common Terminal: The COM of the binary input/output (transistor) is common to the cathode.
  • Desmontaje: Do not disassemble the product or modify the wiring optionally. Otherwise, it may cause fault, malfunction, loss of time.
  • Daño: Make sure to turn off all power when you install or dismantle the product, otherwise it may cause malfunction or fault.

6. Especificaciones

The following table details the specifications for the QM3G-50FH model and other related models in the series.

Detailed specifications and parameters table for Coolmay QM3G HMI PLC models, including display size, resolution, dimensions, memory, I/O types, high-speed counting, analog inputs/outputs, and communication ports.

Figure 13: Specifications and Parameters Table.

General Specifications (QM3G-50FH)

CaracterísticaDescripción
Pantalla de visualización5" TFT LCD screen
Resolución800*480
Dimensiones151*96*36 mm
Tamaño del recorte143*86 mm
Tamaño de la pantalla108*65 mm
Brillo300 cd/m²
Relación de contraste400:1
Iluminar desde el fondoCONDUJO
Color de la pantalla65536 color verdadero
Tipo táctil4-wire resistive panel
ROM (Flash)Memoria flash NOR de 16 MB
RAM64 MB
UPC408 MHz
Dispositivo USBUSB 2.0 (Tipo C)
Puerto serialRS-232
I/O Type (Digital)Transistor output: low level NPN, COM connected to negative; Relay output: normally open dry contact.
Conteo de alta velocidad6 channel 60KHz, 2 channel 10KHz, 1 channel 60KHz
High-speed Pulse8 channel 10KHz, 4 channel 100KHz
Analog Input Types (Optional)PT100/PT1000/Thermocouple/NTC/0-5V/0-10V/0-20mA/4-20mA
Analog Output Types (Optional)0-5V/0-10V/0-20mA/4-20mA
Peso600 gramos
Dimensiones del paquete25 cm (largo) x 15 cm (ancho) x 10 cm (alto)

7. Garantía y soporte

For warranty information, technical support, and service inquiries, please refer to the official Coolmay website or contact your authorized dealer. This manual provides operational guidance and does not cover specific warranty terms or support procedures.

Additional resources, including detailed HMI and PLC programming manuals, can be found on the Coolmay official website or through your supplier.

Documentos relacionados - QM3G-50FH-24MT/R

Preview Manual de programación todo en uno HMI/PLC serie QM3G de Coolmay: características, especificaciones y guía de funcionamiento
This comprehensive programming manual details the Coolmay QM3G Series HMI/PLC All-in-one devices. It covers hardware specifications, programming precautions, PLC and HMI functionalities, communication protocols (Modbus, RS485, CAN, Ethernet), and software usage, providing essential information for engineers and technicians working with Coolmay's industrial automation solutions.
Preview Manual de usuario del PLC HMI Coolmay QM3G-FH todo en uno
Manual de usuario para los productos HMI PLC todo en uno de la serie Coolmay QM3G-FH, que detalla las características, especificaciones, cableado y referencias de programación para la automatización industrial.
Preview Manual de programación del PLC Coolmay V20.81 - Instrucciones y operaciones
Manual de programación completo para los controladores de la serie Coolmay PLC (V20.81), que detalla las instrucciones, el funcionamiento del dispositivo y los principios de programación. Compatible con el software de Mitsubishi.
Preview HMI industrial Coolmay TK6043BH de 4.3": características, especificaciones y manual del usuario
Información detallada sobre la HMI Coolmay TK6043BH de 4.3 pulgadas, incluidas características del producto, especificaciones técnicas, dimensiones del contorno, definiciones de terminales y pautas de instalación para el usuario.
Preview Guía del usuario de la plataforma Coolmay Cloud: Registro, vinculación y configuración
Una guía completa para usar la plataforma Coolmay Cloud para la operación remota de PLC, que abarca el registro de cuentas, la vinculación de dispositivos, la configuración de variables esclavas y la configuración de parámetros de red. Este documento detalla los pasos para integrar los PLC Coolmay con la nube para una monitorización y un control mejorados.
Preview Guía de instalación y configuración de COOLMAY HMI
Una guía completa para instalar, configurar y usar COOLMAY HMI con Arduino, que cubre la configuración del controlador, el direccionamiento IP, la configuración del software y la ejecución de Modbus TCP.ampLes.