Intermatic FM1STUZH-240U

Manual de instrucciones del módulo temporizador electromecánico Intermatic FM1STUZH-240U

Model: FM1STUZH-240U

1. Introducción

The Intermatic FM1STUZH-240U is a 24-hour electromechanical timer module designed for precise control of electrical loads. This module features a Single-Pole Double-Throw (SPDT) switch with a 21 Amp rating at 240V, making it suitable for various applications such as heating, ventilation, air conditioning, refrigeration, lighting, security, circulating pumps, spas, and other electrical loads requiring 24-hour scheduling. It includes a manual override switch for temporary control.

2. Información de seguridad

WARNING: Risk of electric shock. This product must be installed by a qualified electrician in accordance with all national and local electrical codes.

3. Características

4. Especificaciones

EspecificaciónValor
Número de modeloFM1STUZH-240U
Vol de suministrotage240 VAC, 60 Hz
Consumo de energía1 VA
Tipo de interruptorSPDT (Single-Pole Double-Throw)
Calificación resistiva21A @ 120-250 VAC
Clasificación del motor1 HP @ 120 VAC, 2 HP @ 250 VAC
Clasificación de tungsteno1350 W a 240 VCA
Tiempo mínimo de encendido/apagado15 minutos
Conexiones de cableado1/4-inch Quick-Connect Terminals
Temperatura de funcionamiento-40 °F a 185 °F (-40 °C a 85 °C)
Dimensiones (alto x ancho x profundidad)2.36" x 2.36" x 1.25" (60 mm x 60 mm x 32 mm)
InstalaciónMontaje en panel
Batería de respaldoNone (Synchronous drive)

5. Instalación

The FM1STUZH-240U timer module is designed for panel mounting within an appropriate enclosure. Ensure the enclosure provides adequate protection for the operating environment.

5.1 Montaje

Mount the timer module securely to the panel using appropriate fasteners. Refer to the product dimensions for proper cutout and spacing.

Frente view of Intermatic FM1STUZH-240U Electromechanical Timer Module

Figura 1: Frente view of the FM1STUZH-240U timer module, showing the 24-hour dial and manual override switch.

5.2 conexiones de cableado

Before making any connections, ensure power is disconnected at the main circuit breaker. The timer module uses 1/4-inch quick-connect terminals. Refer to the wiring diagram below and the labels on the timer for correct connections.

Atrás view of Intermatic FM1STUZH-240U Electromechanical Timer Module with quick-connect terminals

Figura 2: Atrás view of the FM1STUZH-240U timer module, showing the quick-connect terminals for wiring.

Conexiones de terminales:

Connect the load according to your application's requirements, utilizing the COM, NO, and NC terminals as needed. Always verify connections before restoring power.

6. Configuración

6.1 Configuración de la hora actual

  1. Rotate the dial clockwise until the current time aligns with the time arrow (indicator mark) on the timer face.
  2. The dial is marked in 24-hour format (e.g., 12 = noon, 18 = 6 PM, 24/0 = midnight).

6.2 Configuración de horarios de encendido y apagado

The timer dial has 96 captive trippers, each representing 15 minutes. To set ON/OFF times:

7. Operación

7.1 Operación automática

Once the current time and ON/OFF trippers are set, the timer will automatically switch the connected load according to the programmed schedule. The dial will continuously rotate, and the internal switch will change state as the trippers engage or disengage.

7.2 Anulación manual

The FM1STUZH-240U includes a manual override switch for temporary control of the connected load, independent of the programmed schedule. The override switch has three positions:

To use the manual override, simply move the switch to the desired position. Remember to return it to the automatic (center) position for programmed operation to resume.

8. Mantenimiento

The Intermatic FM1STUZH-240U timer module is designed for long-term, reliable operation with minimal maintenance.

Always disconnect power before performing any inspection or cleaning inside the enclosure.

9. Solución de problemas

If the timer module is not functioning as expected, perform the following basic checks:

If issues persist after performing these checks, it is recommended to contact a qualified electrician or Intermatic customer support for further assistance.

10. Garantía y soporte

For warranty information and technical support, please refer to the official Intermatic webSitio web o contacte con el departamento de atención al cliente. Conserve su recibo de compra como comprobante.

Documentos relacionados - FM1STUZH-240U

Preview Interruptor horario de 24 horas Intermatic T105: Guía de instalación, cableado y funcionamiento
Guía completa del temporizador mecánico de 24 horas Intermatic T105. Incluye especificaciones del modelo, advertencias de seguridad, instrucciones de cableado para diversas configuraciones (SPNO, SPNC, SPDT), procedimientos de programación y operación manual. Incluye una tabla detallada de especificaciones eléctricas y recomendaciones de calibre de cable.
Preview Temporizador de pared Intermatic serie KM2: Instrucciones de instalación y funcionamiento
Guía completa para la instalación y el funcionamiento de los temporizadores de pared Intermatic serie KM2. Conozca las características, especificaciones, programación y cableado para el control automático de iluminación y otros circuitos.
Preview Temporizadores para calentadores de agua Intermatic serie WHQ de 40 A con batería de respaldo - Manual de instalación y funcionamiento
Información detallada sobre los temporizadores electromecánicos para calentadores de agua de la serie WHQ de Intermatic, con funciones de 24 horas/7 días, incluyendo características, especificaciones, guía de instalación, instrucciones de programación e información sobre la garantía. Diseñados para uso residencial, comercial e industrial.
Preview Intermatic MIL72 Series 24-Hour Mechanical Timer Switches
Encimaview of Intermatic MIL72 Series 24-Hour mechanical timer switches, detailing features, specifications, and applications for lighting control, HVAC, and general electrical circuits.
Preview Interruptor horario comercial electromecánico Intermatic serie GM40AV: Manual de instalación y funcionamiento
Guía completa de instalación, operación y programación de los interruptores horarios electromecánicos comerciales Intermatic serie GM40AV. Incluye especificaciones eléctricas, diagramas de cableado e información sobre la garantía.
Preview Interruptor horario de 24 horas con interruptor de bomberos Intermatic T101P201/T101R201
Guía detallada para los interruptores horarios de 24 horas Intermatic T101P201 (plástico) y T101R201 (metal) con función de interruptor de bomberos para calentadores de piscina. Incluye instrucciones de cableado, programación y funcionamiento.