Simplex S4099-9006

Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station

Modelo: S4099-9006

1. Introducción

This manual provides comprehensive instructions for the installation, operation, and maintenance of the Simplex 4099-9006 Double Action, Push Pull Down Fire Alarm Station. This device is designed to initiate a fire alarm signal when manually activated, contributing to the overall safety and security of a building's occupants.

The Simplex 4099-9006 is an IDNet addressable manual pull station with an integrated LED indicator, ensuring reliable communication within compatible fire alarm systems.

2. Información de seguridad

WARNING: Installation and servicing of this device must be performed by qualified personnel only, in accordance with all local and national electrical codes, and the National Fire Alarm and Signaling Code (NFPA 72).

  • Always disconnect power to the fire alarm control panel before installing or servicing the pull station.
  • Asegure una conexión a tierra adecuada para evitar descargas eléctricas.
  • Do not paint over the pull station or obstruct its operation.
  • Test the pull station regularly as part of a comprehensive fire alarm system testing schedule.
  • This device is not intended for outdoor use unless specifically rated for such environments.

3. Producto terminadoview

The Simplex 4099-9006 is a robust, red-colored manual fire alarm pull station featuring a double-action mechanism (push then pull). It includes an integrated LED indicator for status feedback.

Simplex 4099-9006 Double Action Fire Alarm Pull Station with installation instructions

Figure 3.1: Simplex 4099-9006 Double Action Fire Alarm Pull Station. This image displays the front of the red pull station with "FIRE ALARM" and "PUSH PULL DOWN" labels, alongside a detailed instruction sheet for installation and mounting, and a small bag of mounting hardware.

Los componentes clave incluyen:

  • Activation Handle: The "PUSH PULL DOWN" mechanism used to initiate an alarm.
  • Indicador LED: Provides visual status of the device (e.g., normal, alarm, trouble).
  • Bloque de terminales: For connecting to the fire alarm control panel's IDNet circuit.
  • Mounting Plate/Housing: Secures the device to a standard electrical box or surface.

4. Configuración e instalación

The Simplex 4099-9006 pull station can be installed using either single-gang or two-part mounting methods, typically on a standard 4-inch square electrical box (not supplied).

4.1 Comprobaciones previas a la instalación

  • Verify that the fire alarm control panel is powered off.
  • Ensure the mounting location is clean, dry, and meets local code requirements for height and accessibility.
  • Confirm all necessary tools and hardware are available (e.g., screwdriver, wire strippers, mounting screws).

4.2 Procedimientos de montaje

Refer to the installation diagrams provided with the product and shown in Figure 3.1 for visual guidance.

4.2.1 Single-Gang Mounting

  1. Secure the pull station directly to a standard single-gang electrical box.
  2. Ensure the device is flush with the wall surface.

4.2.2 Two-Part Mounting

  1. Install the backbox or mounting plate first, typically a 4-inch square electrical box.
  2. Mount the pull station assembly onto the installed backbox.
  3. This method may be used for flush trim or surface mounting applications.

4.3 Cableado

The 4099-9006 is an IDNet addressable device. Connect the pull station to the IDNet circuit of the fire alarm control panel using appropriate gauge wiring, following the wiring diagram provided on the device or in its specific installation sheet. Ensure polarity is correct.

  • Connect the incoming and outgoing IDNet circuit wires to the designated terminals.
  • Asegúrese de que todas las conexiones estén seguras y libres de cortocircuitos.

4.4 Post-instalación

  • Once installed and wired, restore power to the fire alarm control panel.
  • Verify the LED indicator on the pull station shows a normal operating status (typically a slow flash).
  • Perform a functional test of the pull station as described in the "Operating Instructions" section.

5. Instrucciones de funcionamiento

The Simplex 4099-9006 features a double-action activation mechanism to prevent accidental alarms.

5.1 Activación de la alarma

  1. EMPUJAR: Firmly push the "PUSH" bar located at the top of the activation handle.
  2. DERRIBAR: Once the "PUSH" bar is depressed, pull the handle "PULL DOWN" until it latches in the alarm position.
  3. Upon activation, the pull station will send an alarm signal to the fire alarm control panel, and the integrated LED will illuminate steadily (or change to a rapid flash, depending on system programming) to indicate an alarm state.

5.2 Restablecimiento de la estación de tiro

To reset the pull station after an alarm, a special key (not included with this specific model, as indicated by "No Key" in the product title, implying a different reset mechanism or system-level reset) or tool is typically required to return the handle to its normal, non-alarm position. For the 4099-9006, the reset mechanism is internal and does not require a key. Simply push the handle back into its original position. The fire alarm control panel must also be reset to clear the alarm condition from the system.

6. Mantenimiento

Regular maintenance ensures the reliable operation of your Simplex 4099-9006 pull station. All maintenance should be performed by qualified personnel.

6.1 Controles de rutina

  • Inspección visual (mensual): Check for any physical damage, obstructions, or signs of tampering. Ensure the pull station is clean and clearly visible.
  • LED Status (Monthly): Verify the LED indicator is showing a normal operating status (e.g., slow flash).

6.2 Functional Testing (Annually or as per local codes)

Functional testing should be conducted by a certified fire alarm technician.

  1. Notify building occupants and the monitoring station before testing.
  2. Activate the pull station as described in "Operating Instructions".
  3. Verify that the fire alarm control panel receives the alarm signal and initiates appropriate responses (e.g., sounding alarms, notifying monitoring station).
  4. Reset the pull station and the fire alarm control panel.
  5. Confirm the pull station returns to a normal operating state.

6.3 Limpieza

Limpie el exterior de la estación de tiro con un paño suave.amp Paño. No utilice limpiadores abrasivos ni disolventes, ya que pueden dañar el acabado o los componentes internos.

7. Solución de problemas

This section addresses common issues you might encounter with the Simplex 4099-9006 pull station. For complex issues, contact a qualified fire alarm technician.

ProblemaPosible causaSolución
Pull Station does not activate alarm.Incorrect activation procedure; wiring issue; device fault; control panel issue.Ensure proper push-then-pull action. Check wiring connections. Verify control panel status. Contact technician if problem persists.
LED indicator is off or shows trouble.No power; wiring fault; device fault; control panel trouble.Check power to the control panel. Inspect wiring for breaks or shorts. Consult control panel manual for trouble codes. Contact technician.
Falsa alarma.Accidental activation; faulty device; wiring issue.Reset the pull station and control panel. Inspect for physical damage or obstructions. If recurring, contact technician.
Pull station handle does not reset.Problema con el mecanismo interno; residuos.Ensure no debris is obstructing the mechanism. Gently attempt to push the handle back. If it remains stuck, the unit may need replacement.

8. Especificaciones

CaracterísticaDetalle
Número de modeloS4099-9006
Tipo de productoDouble Action Manual Fire Alarm Pull Station
MarcaSimplex
FabricanteSIMPLEX Grinnell
ColorRojo
Método de activaciónPush then Pull Down
Key Requirement for ResetNo Key Required (Internal Reset)
ConectividadIDNet Addressable
Funciones integradasIndicador LED
Peso del artículo0.5 libras (aprox. 8 onzas)
Dimensiones del producto6 x 6 x 4 pulgadas (aproximadamente)
Código Postal643485653004
Fecha de primera disponibilidad21 de diciembre de 2015
Simplex 4099-9006 product packaging boxSimplex 4099-9006 product packaging box with PID and Part No.

Figure 8.1: Product packaging for the Simplex 4099-9006, showing the brown cardboard box with product identification labels. The labels confirm PID 4099-9006 and Part No. 06501211.

9. Garantía y soporte

9.1 Información de garantía

This Simplex product is typically covered by a manufacturer's warranty against defects in materials and workmanship. Specific warranty terms and duration may vary. Please refer to the original purchase documentation or contact Simplex customer service for detailed warranty information.

Note: The product listing mentions "12 months warranty" and "30 days return if not satisfied". This information is from a third-party seller and may not reflect the official manufacturer's warranty. Always verify with the manufacturer.

9.2 Soporte técnico

For technical assistance, installation guidance, or troubleshooting beyond the scope of this manual, please contact a certified fire alarm technician or the manufacturer directly.

Simplex Customer Support: Please visit the official SimplexGrinnell websitio o consulte el embalaje de su producto para obtener información de contacto.

Para consultas generales, también puede consultar el Simplex brand page on Amazon.

Documentos relacionados - S4099-9006

Preview Estaciones de alarma contra incendios manuales direccionables Simplex IDNet/MAPNET II - Datos del producto
Información detallada sobre las estaciones de alarma contra incendios manuales direccionables Simplex Serie 4099, compatibles con los sistemas IDNet y MAPNET II. Características, especificaciones, opciones de montaje y selección de productos para diversos modelos, incluyendo opciones de acción simple, doble acción (rompible y pulsador) y sin agarre. Cumple con los requisitos de la ADA y está homologado por UL, ULC, FM y CSFM.
Preview Estaciones manuales direccionables simplex: periféricos IDNet/MAPNET II
Explore las estaciones de alarma contra incendios manuales direccionables Simplex, detallando sus características, tipos de acción simple/doble, opciones SIN AGARRE y compatibilidad con sistemas IDNet/MAPNET II. Incluye información de montaje y especificaciones.
Preview Hoja de datos de las estaciones de alarma contra incendios manuales de acción simple y doble de la serie Simplex 2099
Hoja de datos de las estaciones manuales de alarma contra incendios Simplex serie 2099, no codificadas y no direccionables. Describe características, tipos de operación, referencias de aplicaciones, selección de productos, opciones de montaje y especificaciones.
Preview Simplex 4010ES: Sistemas de comando de extinción automática para gicleurs
Guide Technique Simplex 4010ES detalla los módulos de comando para los sistemas de extinción automática por gicleurs, cubre los modos de diluvio y prevención, con especificaciones, homologaciones y esquemas de cableado.
Preview Panel de control de alarma contra incendios Simplex 4004: Instrucciones de instalación y funcionamiento
Guía completa para instalar, operar y programar el panel de control de alarma contra incendios Simplex 4004 (FACP), incluido el sistemaview, requisitos, cableado, descripciones de módulos y solución de problemas.
Preview Ficha técnica de la unidad de control de incendios Simplex 4010ES: sistemas de extinción automática, diluvio y rociadores de preacción
Hoja de datos técnicos de la unidad de control de incendios Simplex 4010ES, que detalla sus capacidades para extinción automática, diluvio y sistema de rociadores de preacción.asinControl g. Incluye características, especificaciones, listados de agencias y componentes compatibles.