Manual del usuario del detector de fugas de refrigerante con diodo calefactado Fieldpiece DR58

Modelo: DR58

1. Introducción

The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector is an ultra-sensitive tool designed for HVACR professionals to quickly and accurately locate refrigerant leaks. Utilizing a heated diode sensor, it detects a wide range of refrigerants with high precision. This manual provides essential information for the proper setup, operation, maintenance, and troubleshooting of your DR58 leak detector.

Detector de fugas de refrigerante con diodo calefactado Fieldpiece DR58

Image 1.1: The Fieldpiece DR58 Heated Diode Refrigerant Leak Detector, showing its main body and flexible probe.

2. Características principales

The DR58 is equipped with several features to enhance leak detection efficiency:

  • Ultra-Sensitive Heated Diode Sensor: Detects micro leaks as small as <0.03 oz/yr, offering 20 times greater sensitivity than traditional bubble methods.
  • Universal Refrigerant Compatibility: Capable of detecting all HFC, CFC, HCFC, HFO, H2N2 (Tracer Gas), and blended refrigerants used in HVACR systems.
  • Duradero y de larga duración: Features an IP54 rating for resistance against moisture and oil, ensuring reliability in various working conditions. The sensor has a typical life of 300 hours.
  • Clear Leak Indicators: A large, backlit LCD screen displays leak size and intensity using a bar graph and numeric readings. An LED tip and audible beep provide immediate feedback for precise leak pinpointing.
  • Flexible Probe and Extended Battery Life: A 17-inch flexible probe allows access to tight spaces. The rechargeable USB battery provides up to 18 hours of continuous operation. Replaceable filter tips are included.
Features and Benefits of Fieldpiece DR58

Image 2.1: Visual summary of the DR58's features, including its heated diode sensor, backlit LCD, refrigerant compatibility, and durable design.

3. Configuración

Before initial use, ensure the DR58 is properly set up and charged.

3.1 Desembalaje y componentes

Your Fieldpiece DR58 package should include:

  • 1 x Heated Diode Refrigerant Leak Detector (DR58)
  • 5 x Replacement Filtered Tips (RFT6)
  • 1 x Blow-Molded Case
  • 1 x Heated Diode Sensor (RHD1) (pre-installed or separate)
  • 1 x USB Charging Cable and Wall Adapter
What's Included with Fieldpiece DR58

Image 3.1: Contents of the DR58 package, showing the detector, charging cable, filter tips, and case.

3.2 Carga inicial

  1. Connect the USB charging cable to the DR58's charging port.
  2. Plug the other end of the cable into the wall adapter and then into a power outlet.
  3. Allow approximately 6 hours for a full charge. The battery indicator on the LCD will show charging status.

3.3 Sensor and Filter Tip Installation

  1. Asegúrese de que el dispositivo esté apagado.
  2. If the heated diode sensor (RHD1) is not already installed, carefully insert it into the end of the flexible probe until it clicks into place.
  3. Screw a filtered tip onto the end of the sensor. Ensure it is finger-tight to prevent debris from entering the sensor.

4. Operación

Follow these steps for effective leak detection with your DR58.

4.1 Encendido y calentamiento

  1. Press and hold the power button (blue button with sun icon) for approximately 1 second to turn on the device.
  2. The DR58 will display 'Warm' and then 'AZERO' as it warms up and performs an automatic zeroing. This process typically takes less than 10 seconds.

4.2 Puesta a cero del dispositivo

Zeroing establishes a baseline for the ambient air, allowing the detector to accurately identify refrigerant concentrations above this baseline.

  • Automatic Zeroing: The device automatically zeros upon power-on and continuously adjusts to background refrigerant levels during operation.
  • Manual Zeroing: To manually zero the device, move the probe to an area known to be free of refrigerant. Press the 'ZERO MANUAL/AUTO' button. The display will show 'AZERO' to confirm.

4.3 Ajuste de la sensibilidad

The DR58 offers adjustable sensitivity levels to suit different leak detection scenarios.

  • Press the 'SENSITIVITY MAX ON/OFF' button to cycle through sensitivity levels (High, Medium, Low).
  • Use higher sensitivity for smaller leaks or when the leak source is difficult to pinpoint. Use lower sensitivity in areas with higher background refrigerant levels to avoid false positives.

4.4 Procedimiento de detección de fugas

  1. Slowly move the flexible probe along the suspected leak area, such as refrigerant lines, coils, and connections. Maintain a consistent speed of approximately 1-2 inches per second.
  2. Observe la pantalla LCD para ver si hay incrementos.asing bar graph segments and numeric readings, indicating the presence of refrigerant.
  3. Listen for the audible beep, which will increase in frequency and pitch as the leak source is approached.
  4. The LED tip on the probe will also illuminate red, intensifying as the leak concentration increases.
  5. Once a leak is detected, move the probe away from the area and then slowly re-approach to confirm the exact location.
DR58 probe tip with illuminated LED

Image 4.1: Close-up of the DR58's flexible probe tip, showing the illuminated red LED indicator during leak detection.

Video 4.1: An official product video demonstrating the Fieldpiece DR58 leak detector in use, highlighting its features and effectiveness in finding refrigerant leaks.

5. Mantenimiento

Regular maintenance ensures the longevity and accuracy of your DR58.

5.1 Replacing Filter Tips

The filter tips prevent debris from entering the sensor. Replace them regularly, especially in dirty environments, or if they appear clogged.

  1. Unscrew the old filter tip from the sensor.
  2. Screw on a new replacement filter tip (RFT6) until it is finger-tight.

5.2 Reemplazo del sensor

The heated diode sensor (RHD1) has a typical life of 300 hours. Replace the sensor when its performance degrades or if the device indicates a sensor error.

  1. Power off the DR58.
  2. Unscrew the filter tip.
  3. Gently pull the old sensor out of the probe.
  4. Insert the new RHD1 sensor into the probe until it clicks into place.
  5. Re-attach a clean filter tip.

5.3 Limpieza

  • Limpie el exterior del dispositivo con publicidadamp Paño. No utilice limpiadores abrasivos ni disolventes.
  • Ensure the sensor and filter tip are free from oil, moisture, and debris.

6. Solución de problemas

If you encounter issues with your DR58, refer to the following common problems and solutions.

ProblemaPosible causaSolución
El dispositivo no se enciende.Batería baja o agotada.Charge the device using the provided USB cable and adapter.
Lecturas inexactas o inconsistentes.Sensor contaminated or worn out; filter tip clogged; high background refrigerant.Replace filter tip. Replace sensor if necessary. Perform manual zeroing in a clean air environment.
No leak detected despite suspected leak.Low sensitivity setting; probe moved too quickly; sensor issue.Increase sensitivity. Move probe slower. Check and replace sensor if needed.
Constant alarm or high readings in clean air.Device not properly zeroed; sensor contaminated.Perform manual zeroing in a clean air environment. Clean or replace sensor.

7. Especificaciones

Technical specifications for the Fieldpiece DR58 Heated Diode Refrigerant Leak Detector.

Fieldpiece DR58 Specifications

Image 7.1: A detailed list of the DR58's technical specifications, including sensor type, sensitivity, and battery life.

EspecificaciónValor
Tipo de sensorSensor de diodo calentado
Vida del sensor300 horas típicas
Niveles de sensibilidadAlto, medio, bajo (seleccionable)
Máxima sensibilidad0.03 oz/yr (1g/a) stationary; 0.1 oz/yr (3g/a) in motion
Retroalimentación de detecciónLED de punta roja, gráfico de barras LCD, dígitos LCD, zumbador
RefrigerantesHFC, HCFC, CFC, HFO y mezclas
Tiempo de respuesta<1 segundo típico
Tiempo de recuperación<10 segundo típico
Tipo de batería3.7 V CC (nominal) 2550 mAh, no reemplazable
Tiempo de carga6 hours typical with included charger
Duración de la batería18 horas típico, retroiluminación apagada
Apagado automático10 minutos sin detección ni pulsación de botón
Entorno operativo32 ° F a 104 ° F (0 ° C a 40 ° C); <75% RH (sin condensación)
Temperatura de almacenamiento-4 ° F a 140 ° F (-20 ° C a 60 ° C); <80% de humedad relativa
Peso14 oz (400g)
Resistencia al aguaDiseñado para IP54
Dimensiones del producto10 x 8 x 10 pulgadas

8. Garantía y soporte

Fieldpiece Instruments provides a warranty for its products against defects in material and workmanship. For specific warranty terms, registration, and technical support, please refer to the official Fieldpiece webSitio web o contacte directamente con el servicio de atención al cliente. Conserve su recibo de compra como comprobante.

Para obtener más ayuda, visite el Tienda Fieldpiece en Amazon or the official Fieldpiece websitio.

Documentos relacionados - DR58

Preview Manual del operador del detector de fugas de refrigerante con diodo calentado Fieldpiece DR58
Manual del operador del detector de fugas de refrigerante de diodo calentado Fieldpiece DR58, que detalla sus características, especificaciones, funcionamiento, instalación, mantenimiento y pruebas de funcionalidad para detectar diversos refrigerantes.
Preview Manual del operador del detector de fugas de refrigerante Fieldpiece DRX3
Manual del operador completo del detector de fugas de refrigerante Fieldpiece DRX3, que detalla sus características, funcionamiento, precauciones de seguridad, mantenimiento y especificaciones para profesionales de HVAC.
Preview Manual del operador del detector de fugas de refrigerante infrarrojo Fieldpiece DR82
Guía completa del detector infrarrojo de fugas de refrigerante Fieldpiece DR82, que abarca sus características, especificaciones, funcionamiento, mantenimiento y garantía. Aprenda a detectar HFC, HCFC, CFC, HFO y refrigerantes de mezcla con alta sensibilidad y múltiples indicadores.
Preview Manual del operador del detector de fugas de refrigerante infrarrojo Fieldpiece DR82
Manual del operador del detector de fugas de refrigerante infrarrojo (IR) Fieldpiece DR82. Detalla características, especificaciones, funcionamiento, mantenimiento, normas de seguridad e información sobre la garantía para profesionales de HVACR.
Preview Manual del operador del detector de fugas de refrigerante infrarrojo Fieldpiece DR82
Manual del operador completo del detector de fugas de refrigerante infrarrojo (IR) Fieldpiece DR82, que detalla sus características, funcionamiento, mantenimiento y especificaciones para profesionales de HVACR.
Preview Manual del operador del detector de fugas de refrigerante Fieldpiece DRX3
Manual del operador completo para el detector de fugas de refrigerante Fieldpiece DRX3, que detalla sus características, funcionamiento, mantenimiento y pautas de seguridad para detectar fugas de refrigerante y gas combustible.