DAB 60231855

Manual de instrucciones de la bomba circuladora DAB Evosta 2 40-70/130

Model: 60231855 | Brand: DAB

1. Introducción y másview

The DAB Evosta 2 is an electronic, low-energy consumption circulator pump designed for water circulation in various domestic heating and air conditioning systems. This manual provides essential information for the safe and efficient installation, operation, and maintenance of your Evosta 2 pump.

The Evosta 2 series combines the robustness of mechanical circulators with the advantages of electronic control. It features a synchronous permanent magnet motor, a frequency converter, and an efficiency index (EEI) of ≤ 0.18, ensuring high efficiency and reliability. Its compact design and comprehensive performance make it suitable for replacing older three-speed circulators.

DAB Evosta 2 Circulator Pump
Figure 1: DAB Evosta 2 Circulator Pump. This image shows the main unit with its green and black housing, control panel, and threaded connections.

2. Información de seguridad

Importante: Lea todas las instrucciones de seguridad antes de instalar o usar el producto. No seguir estas instrucciones podría provocar una descarga eléctrica, un incendio o lesiones graves.

  • La instalación y el mantenimiento deben ser realizados únicamente por personal calificado.
  • Ensure the power supply is disconnected before performing any work on the pump.
  • The pump operates with hot liquids; allow it to cool before handling to prevent burns.
  • Protect the pump from moisture and direct water spray.
  • No opere la bomba si está dañada o si el cable eléctrico está desgastado.
  • The pump is designed for clean, non-viscous, chemically neutral liquids. Do not use with flammable or corrosive liquids.

3. Descripción y características del producto

The Evosta 2 circulator pump is engineered for optimal performance and durability. Key features include:

  • Eficiencia Energética: Equipped with a synchronous permanent magnet motor and frequency converter, achieving an EEI ≤ 0.18.
  • Construcción robusta: Cast iron pump body with cataphoresis treatment, wet rotor motor, and ceramic shaft mounted on ceramic bushings lubricated by the pumped liquid.
  • Protección integrada: Internal motor protection eliminates the need for external overload protection.
  • Control fácil de usar: A single sequential adjustment button on the control panel simplifies settings.
  • Acceso de mantenimiento: Direct access to the crankshaft for potential unlocking.
  • High Protection Rating: Grado de protección IPX5.
DAB Evosta 2 Features and Benefits
Figura 2: Sobreview of Evosta 2 features, highlighting its energy efficiency (EEI ≤ 0.18) and 5-year warranty. The image also shows different models in the Evosta series.

La bomba casing is made of steel, with a technopolymer impeller. The rotor sleeve, stator sleeve, and closing flange are stainless steel. The thrust ring is graphite, and the sealing rings are EPDM. An air bleed plug made of brass is integrated.

DAB Evosta 2 Exploded View and Materials List
Figura 3: Explosión view of the Evosta 2 pump with a corresponding list of materials for each component, illustrating the internal construction.

4. Instalación

Proper installation is crucial for the pump's performance and longevity. Follow these guidelines:

  • Posición de montaje: Install the pump with the motor axis horizontal.
  • Conexiones de tubería: The Evosta 2 40-70/130 is equipped with 1" (G 1") threaded connections. The 1/2" designation refers to the thread intended for connection to 1" to 1/2" reduced female fittings. Verify compatibility with your existing pipes or fittings.
  • Fuente de alimentación: Connect the pump to a single-phase 1 x 230 V ~ 50/60 Hz power supply. Ensure the electrical installation complies with local regulations.
  • Lavado del sistema: Before starting the pump, ensure the system is thoroughly flushed to remove any debris that could damage the pump.
  • Purga de aire: The pump includes an integrated air bleed plug. After filling the system, open the plug to release any trapped air.

Refer to the dimensional drawings for precise measurements and connection details to ensure proper fitment within your system.

DAB Evosta 2 Dimensional Drawing
Figure 4: Dimensional drawing of the Evosta 2 40-70/130 pump, showing key measurements (in mm) and pump connection details (1" G thread).

5. Operación

The Evosta 2 pump features a control panel on the electronic control device cover, allowing for easy adjustment of its functions. The pump offers nine setting options, selectable via the MODE button.

  • Selección de configuración: Press the MODE button to cycle through the available settings. The selected setting is indicated by six illuminated segments on the display.
  • Modos de funcionamiento: The pump supports various operating modes, typically including proportional pressure, constant pressure, and constant curve modes, to adapt to different system requirements.
DAB Evosta 2 Operating Modes and Settings
Figure 5: Diagram illustrating the different operating modes (Proportional Pressure, Constant Pressure, Constant Curve) and an example of model designation for the Evosta series.

Consult the specific icons or indicators on your pump's control panel to identify the active operating mode and adjust as needed for your heating or cooling system.

6. Mantenimiento

Regular maintenance ensures the long-term reliability and efficiency of your Evosta 2 pump.

  • Purga de aire: Periodically check and, if necessary, open the integrated brass air bleed plug to release any air trapped in the pump. This prevents cavitation and ensures smooth operation.
  • Crankshaft Unlocking: In case of a blockage, the pump provides direct access to the crankshaft for manual unlocking. Refer to the technical diagrams for the exact location.
  • Limpieza: Keep the exterior of the pump clean and free from dust and debris. Do not use abrasive cleaners.
  • System Fluid: Ensure the pumped liquid remains clean and free of solid substances and mineral oils. Glycol content should not exceed 30%.
  • No Overload Protection Needed: Due to internal motor protection, no external overload protection is required.

7. Solución de problemas

If you encounter issues with your Evosta 2 pump, consider the following common problems and solutions:

  • La bomba no arranca:
    • Verifique la fuente de alimentación y el disyuntor.
    • Ensure the pump is properly connected to the electrical mains.
    • Verify that the motor is not seized. Use the direct access to the crankshaft to attempt manual unlocking if necessary.
  • No Flow or Reduced Flow:
    • Check for air in the system. Bleed air using the integrated plug.
    • Inspect for blockages in the pipes or pump impeller.
    • Ensure valves in the system are open.
    • Verify the selected operating mode and setting are appropriate for the system's requirements.
  • Ruido inusual:
    • Noise can indicate air in the system. Purge air.
    • Check for foreign objects in the pump.
    • Ensure the pump is securely mounted and not vibrating excessively.

If problems persist after attempting these solutions, contact qualified service personnel or DAB customer support.

8. Especificaciones técnicas

ParámetroValor
ModeloEvosta 2 40-70/130
Número de pieza del fabricante60231855
Rango de operación0.4 – 3.6 m³/h with head up to 6.9 meters
Rango de temperatura del líquidoDe 0 °C a +110 °C
Presión de funcionamiento10 bares (1000 kPa)
Índice de protecciónIPX5
Clase de aislamientoF
InstalaciónMotor axis horizontal
Fuente de alimentación1 x 230 V ~ 50/60 Hz
Pumped LiquidClean, free of solids/mineral oils, non-viscous, chemically neutral, water-like (max 30% glycol)
Material del cuerpo de la bombaHierro fundido con tratamiento de cataforesis.
Motor Casing MaterialAcero
Material del impulsorTecnopolímero
Material del ejeCerámico
Peso1.86 kilogramos
Dimensiones del paquete15 x 14 x 10 cm
DAB Evosta 2 Performance Curves and Data Table
Figure 6: Performance curves and detailed technical data table for various Evosta 2 models, including flow rate (Q) and head (H) values.

9. Garantía y soporte

The DAB Evosta 2 circulator pump comes with a 5 año de garantía, ensuring peace of mind regarding its quality and durability. This warranty covers manufacturing defects under normal use conditions.

For technical assistance, warranty claims, or spare parts inquiries, please contact your authorized DAB dealer or customer support. When contacting support, please have your model number (60231855) and purchase date available.

Information regarding the availability of spare parts is not provided in the product data. Please consult your dealer for specific spare part availability.

Documentos relacionados - 60231855

Preview Circuladores electrónicos de la serie DAB Evosta: Especificaciones técnicas y datos
Especificaciones técnicas completas, características y datos de los circuladores electrónicos DAB Evosta 2, Evosta 3, Evosta 2 SAN y Evosta 2 SOL para sistemas domésticos de calefacción, refrigeración y energía solar.
Preview Circuladores de rotor húmedo DAB BPH/BMH/DPH/DMH: Especificaciones técnicas y datos de rendimiento
Especificaciones técnicas detalladas, curvas de rendimiento, datos eléctricos e información de materiales para las bombas circuladoras de rotor húmedo de las series BPH, BMH, DPH y DMH de DAB, diseñadas para sistemas de calefacción y aire acondicionado.
Preview Bombas circuladoras de la serie DAB EVOSTA: Guía de instalación y mantenimiento
Guía completa para la instalación y el mantenimiento de las bombas circuladoras DAB EVOSTA2, EVOSTA3 y EVOSTA2 SOL. Conozca las características, datos técnicos, seguridad y modos de funcionamiento para sistemas de calefacción y aire acondicionado eficientes.
Preview Catálogo General DAB 2019: Soluciones Tecnológicas del Agua
Explore el completo Catálogo General DAB 2019, que incluye una amplia gama de soluciones de tecnología hidráulica, incluyendo bombas para presurización, calefacción, aguas residuales, piscinas y riego. Descubra el innovador sistema D.Connect para control remoto y gestión inteligente de edificios.
Preview Guía rápida de la bomba circuladora DAB EVOSTA2 SOL: instalación y seguridad
Una guía rápida y concisa para las bombas circuladoras de la serie DAB EVOSTA2 SOL, que detalla las advertencias de seguridad esenciales y la instalación.view, especificaciones del producto e información de contacto para aplicaciones solares y de calefacción doméstica.
Preview Manual de instalación y mantenimiento del módulo de expansión multifunción DAB EVOPLUS SMALL
Este manual proporciona instrucciones detalladas para la instalación, uso y mantenimiento del módulo de expansión multifunción DAB EVOPLUS SMALL, diseñado para mejorar la funcionalidad de los circuladores EVOPLUS SMALL.