INTERRA iX7 Touch Panel

Presupuesto
- Código del producto: ITR165-X0X4
- Fuente de alimentación: 12-30 VDC or PoE+
- Consumo de corriente nominal: 350 mA @12 VDC
- Consumo máximo de corriente: 640 mA @12 VDC
- Communication Current (from KNX Bus): 5 mA
- Consumo de energía nominal: 4.2 W a 12 VCC
- Max. El consumo de energía: 7.7 W a 12 VCC
- UPC: ARM Cortex-A53 de cuatro núcleos
- Memoria: 2 GB DDR3
- Almacenamiento: Memoria EMMC de 8 GB
- Sistema operativo: Interra Operation System based on AOSP 7.1
- Tipo de protección: IP20
- USB: 2 x USB2.0
- KNX: 1 x KNX Connector
- Periféricos: Temp/Hum Sensor, MEMS Microphone
- Botón: Botón de reinicio
- Red: 100Mbps Ethernet
- Tiempo de respuesta: Real Time Clock up to 5 days
- Entrada y salida de GP: 6 Digital Dry Contact Inputs (the Sixth input supports Digital/Analog Mode), 6 Relay Outputs
- Rango de temperatura:
- Funcionamiento: 0°C a 45°C
- Almacenamiento: -15 ° C a 70 ° C
- Dimensiones:
- Panel: 125 x 210 x 54.15 mm (W x H x D)
- Mounting Box: 116 x 201 x 65 mm (W x H x D)
- Configuración: With Interra Configurator Software
DESCRIPCIÓN
Interra iX7 touch panel is designed to control the entire automation system from a single smart point. Interra İX7 can control complex systems such as switches, simple sensors, lighting, camera systems, and alarm systems from a central point. Moreover, iX7 can also control the air conditioning systems with 2 2-point mode by thermostat functionality. Mobile control can be done by downloading InterraX software from online software markets related to IOS or Android-based devices. Also, the configuration software (Interra Configurator) can be downloaded from our websitiowww.interratechnology.com) for the iX7 touch panel configuration.
MODELS AND VARIATIONS

MAIN FUNCTIONAL CHARACTERISTICS
- Automation Control: Control EIO (IO Module controlled over ethernet) and KNX automation systems with the Interra Touch Panel.
- Función de temporizador: Schedule operations daily, weekly, monthly, or annually using the panel s timer.
- Control de seguridad: Manage security systems and view cameras via the panel and mobile apps.
CONEXIONES 
Volumentage: The panel is powered with 12 12-30 VDC via 2 2-pos red coloured connectors. The connector label shows the correct polarity for cable connections.
KNX: The panel has a blue 2 2-pos connector for the KNX port. The connector label shows the correct polarity for cable connections.
USB: The iX7 features two USB host connectors on the side panel for storage expansion.
Ethernet: The panel includes a standard 10/100Mbps RJ45 Ethernet connector.
E/S: The panel has 6 digital dry contact inputs and 6 relay outputs, Input 6 (the sixth input) input)” can operate in digital or analog mode. A temperature sensor can be connected to input 6. Output relay contacts capable of driving 250VAC 5A resistive loads. 
Nota: Input 6 operates in analog or digital mode on products that support analog functionality.
DIMENSIONES
Luntage Box: 
Dispositivo

CARACTERÍSTICAS GENERALES 
MONTAJE
- First, the mounting box must be attached to a suitable place on the wall. The long side of the mounting box should be placed at a right angle to the ground.
- Then, iX7 is attached to the mounting box as shown in the left figure, and the mounting process is completed.

INSTRUCCIONES DE SEGURIDAD
- El dispositivo sólo puede ser instalado y puesto en funcionamiento por un electricista cualificado o personal autorizado.
- For planning and construction of electrical installations, the appropriate specifications, guidelines, and regulations in force in the respective country must be followed.
- No conecte el volumen principaltage (230 VAC) or any other external voltages to any point of the KNX bus.
- Conexión de un volumen externotage might put the KNX system at risk. Please do not overlook this issue.
- Ensure there is sufficient insulation between the 230 VAC voltage cables and the KNX bus.
- The maximum screwing torque value should be 1.2 Nm during the mounting process of the mount case and touch panel.
- Do not use aerosol sprays, solvents, or abrasives that might damage the device.
- Se debe garantizar la accesibilidad del dispositivo para su funcionamiento y su inspección visual.
Documentos / Recursos
![]() | iX7 Touch Panel |
Referencias
- interratechnology.comwww.interratechnology.com
- Manual de usuariomanual.tools